Notice A: Correct connection method for SKP-BC32/40HL _IO signal – 20220321

Dear Partners,

Due to growing demand for automated in assembly production, the application of I/O signal is becoming more and more common adopted, therefore, in order to avoid the risk of controller abnormality of SKP-BC32/40HL caused by incorrect connection, please refer the file as correct connection method as attached.

Mainly is in the input partial, since the design of KILEWS SKP-BC32/40HL controller transistor is belong NPN type, hence if the customer’s PLC or sensor is belong PNP type, please install a relay in between as to avoid the risk of damage to the components in the controller by high potential (voltage).

Thank you very much for your kind attention.

P.S. Your confirmation of the message by return is necessary for us, thanks for your cooperation

Best Regards,